Fixed Orifice DZR Brass commissioning valve, threaded FxF, with integrated test points.
Key Information
- For temperatures below 0°C, use only with water containing anti-freezing additives.
- For temperatures above 100°C, use only with water containing anti-boiling additives.
- PN25 rated: max 25 Bar up to 100°C, max 20 Bar at 130°C.
- Nominal Kvs tolerance of ±3%, tested in accordance with BS7350.
| VIP Code | DN | Size | Flow Range (l/s) |
|---|---|---|---|
| 00/0102/015/EULF | 15 | 1/2″ | 0.0075 – 0.023 |
| 00/0102/015/ULF | 15 | 1/2″ | 0.017 – 0.045 |
| 00/0102/015/LF | 15 | 1/2″ | 0.031 – 0.074 |
| 00/0102/015 | 15 | 1/2″ | 0.062 – 0.148 |
| 00/0102/020 | 20 | 3/4″ | 0.138 – 0.325 |
| 00/0102/025 | 25 | 1″ | 0.258 – 0.603 |
| 00/0102/032 | 32 | 1 1/4″ | 0.540 – 1.250 |
| 00/0102/040 | 40 | 1 1/2″ | 0.810 – 1.880 |
| 00/0102/050 | 50 | 2″ | 1.520 – 3.510 |
VIP DZR Fixed Orifice Balancing Valve Complete with Test Points
The VIP DZR balancing valve is designed for flow measurement and commissioning in heating, cooling and water circulation systems. Featuring a fixed orifice design and supplied complete with test points, this valve helps engineers measure flow rates and assess system performance during commissioning and maintenance.
Key Features and Benefits
- DZR brass construction: Manufactured using dezincification-resistant materials for suitable water system applications.
- Fixed orifice design: Supports accurate flow measurement when used with the appropriate commissioning equipment.
- Test points included: Allows differential pressure measurements to be taken to help determine flow rates.
- PN25 pressure rating: Rated up to 25 bar at temperatures up to 100°C, with a maximum pressure of 20 bar at 130°C.
- BS 7350 design: Designed in accordance with the BS 7350 standard.
- Threaded female connections: Available in a range of sizes to suit different installation requirements.
Applications of a DZR Balancing Valve
A DZR balancing valve is used in water-based heating and cooling systems where monitoring and balancing flow rates is important. During commissioning, engineers can use the valve’s test points with a suitable differential pressure measuring instrument to assess water flow through the system.
Correct flow measurement can help engineers identify whether a system is operating within its intended design parameters. This makes fixed orifice balancing valves useful in suitable commercial heating, cooling and building services installations.
Selecting the Correct Balancing Valve
The VIP DZR Fixed Orifice Balancing Valve is available in multiple connection sizes, with specified flow ranges for different applications. Before ordering, check the required connection size, expected flow rate, operating temperature and system pressure to ensure the selected valve is suitable.
The valve has a nominal Kvs tolerance of ±3%, tested in accordance with BS 7350. Water operating temperatures range from -10°C to 130°C, subject to the manufacturer’s stated conditions. Below 0°C, water must contain suitable antifreeze fluid; above 100°C, suitable anti-boiling fluid is required.
Explore the VIP commissioning valve range for additional balancing and flow measurement products for heating and cooling systems.